Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
10,707
Code Required Method:
1/300 (EXCEPTION)
Calculation:
10,707 ÷ 300 = 35.69 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
35.69
Calculation:
35.69 x 144 = 5,139.36 sq. in. of Code Required Ventilation
Square Inches Provided:
(54 x 98.75) = 5,332.50 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.