Total Vents:
2
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
1,490
Low / Intake Vents:
(Within Lower 1/3 of Attic)
1,490
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
223,423
Code Required Method:
1/150 (EXCEPTION)
Calculation:
223,423 ÷ 150 = 1,489.49 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
1,489.49
Calculation:
1,489.49 x 144 = 214,486.56 sq. in. of Code Required Ventilation
Square Inches Provided:
(2 x 72) = 144 sq. in.
clay Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.
Vent Solutions