Total Vents:
30
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
15
Low / Intake Vents:
(Within Lower 1/3 of Attic)
15
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2,973
Code Required Method:
1/150 (EXCEPTION)
Calculation:
2,973 ÷ 150 = 19.82 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
19.82
Calculation:
19.82 x 144 = 2,854.08 sq. in. of Code Required Ventilation
Square Inches Provided:
(30 x 98.75) = 2,962.50 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.