Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
620'
Required Method:
1/150
Calculation:
620 ÷ 150 = 4.13 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
4.13
Calculation:
4.13 x 144 = 594.72 sq. in of Code Required Ventilation
Square Inches Provided:
(8 x 86.25) = 690 sq. in
Square Inches Needed:
4.13 x 144 = 594.72 sq. in
Where do I install vents graphic
Vent Placement
High / Exhaust Vents Needed:
4
Low / Intake Vents Needed:
4
Total Vents Needed:
8
clay Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
Wire Mesh 86.25 sq. in
Figures based on independent evaluation reports.