Address:
6865 Granada Drive, Redding, CA 96002
Total Vents:
10
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
5
Low / Intake Vents:
(Within Lower 1/3 of Attic)
5
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,770
Code Required Method:
1/300 (EXCEPTION)
Calculation:
1,770 ÷ 300 = 5.90 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
5.90
Calculation:
5.90 x 144 = 849.60 sq. in. of Code Required Ventilation
Square Inches Provided:
(10 x 98.75) = 987.50 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.