Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
7000'
Required Method:
1/150
Calculation:
7000 ÷ 150 = 46.67 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation
46.67
Calculation:
46.67 x 144 = 6720.48 sq. in of Code Required Ventilation
Select Material and Determine Vents Required
Material:
concrete Tile
Placement
Square Inches Provided:
(94 x 72) = 6768 sq. in
Square Inches Needed:
46.67 x 144 = 6720.48 sq. in
High / Exhaust Vents Needed:
47
Low / Intake Vents Needed:
47
Total Vents Needed:
94
Material:
concrete Tile
Product:
Low Profile - "Flat"
Tile Roof Drawing