Total Vents:
36
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
18
Low / Intake Vents:
(Within Lower 1/3 of Attic)
18
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
3,500
Code Required Method:
1/150 (EXCEPTION)
Calculation:
3,500 ÷ 150 = 23.33 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
23.33
Calculation:
23.33 x 144 = 3,359.52 sq. in. of Code Required Ventilation
Square Inches Provided:
(36 x 97.50) = 3,510 sq. in.
concrete Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?