Address:
4525 Northstar Street, Rocklin, Ca
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1965'
Required Method:
1/300
Calculation:
1965 ÷ 300 = 6.55 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
6.55
Calculation:
6.55 x 144 = 943.20 sq. in of Code Required Ventilation
Square Inches Provided:
(14 x 72) = 1008 sq. in
Square Inches Needed:
6.55 x 144 = 943.20 sq. in
Where do I install vents graphic
Vent Placement
High / Exhaust Vents Needed:
7
Low / Intake Vents Needed:
7
Total Vents Needed:
14
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
Wire Mesh 72 sq. in
Figures based on independent evaluation reports.