1672 norte way, santa rosa
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2984'
Required Method:
1/150
Calculation:
2984 ÷ 150 = 19.89 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
19.89
Calculation:
19.89 x 144 = 2864.16 sq. in of Code Required Ventilation
Square Inches Provided:
(40 x 72) = 2880 sq. in
Square Inches Needed:
19.89 x 144 = 2864.16 sq. in
Where do I install vents graphic
Vent Placement
High / Exhaust Vents Needed:
20
Low / Intake Vents Needed:
20
Total Vents Needed:
40
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
Wire Mesh 72 sq. in
Figures based on independent evaluation reports.
Comp Roof Drawing