Address:
615 Hot Springs Rd. - Garage
Total Vents:
4
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
2
Low / Intake Vents:
(Within Lower 1/3 of Attic)
2
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
530
Code Required Method:
1/300 (EXCEPTION)
Calculation:
530 ÷ 300 = 1.77 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
1.77
Calculation:
1.77 x 144 = 254.88 sq. in. of Code Required Ventilation
Square Inches Provided:
(4 x 86.25) = 345 sq. in.
clay Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?