Total Vents:
4
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
2
Low / Intake Vents:
(Within Lower 1/3 of Attic)
2
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
208
Code Required Method:
1/150 (EXCEPTION)
Calculation:
208 ÷ 150 = 1.39 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
1.39
Calculation:
1.39 x 144 = 200.16 sq. in. of Code Required Ventilation
Square Inches Provided:
(4 x 72) = 288 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.