Total Vents:
148
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
74
Low / Intake Vents:
(Within Lower 1/3 of Attic)
74
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
30,448
Code Required Method:
1/300 (EXCEPTION)
Calculation:
30,448 ÷ 300 = 101.49 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
101.49
Calculation:
101.49 x 144 = 14,614.56 sq. in. of Code Required Ventilation
Square Inches Provided:
(148 x 98.75) = 14,615 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.