Address:
636 Havana Avenue (Area 1)
Total Vents:
20
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
10
Low / Intake Vents:
(Within Lower 1/3 of Attic)
10
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,675.50
Code Required Method:
1/150 (EXCEPTION)
Calculation:
1,675.50 ÷ 150 = 11.17 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
11.17
Calculation:
11.17 x 144 = 1,608.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(20 x 97.50) = 1,950 sq. in.
clay Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.