Address:
5595 VIA CALVILLO BONSALL CA.
Total Vents:
18
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
9
Low / Intake Vents:
(Within Lower 1/3 of Attic)
9
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
3,064
Code Required Method:
1/300 (EXCEPTION)
Calculation:
3,064 ÷ 300 = 10.21 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
10.21
Calculation:
10.21 x 144 = 1,470.24 sq. in. of Code Required Ventilation
Square Inches Provided:
(18 x 97.50) = 1,755 sq. in.
clay Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?