Total Vents:
48
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
24
Low / Intake Vents:
(Within Lower 1/3 of Attic)
24
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
4,760
Code Required Method:
1/150 (EXCEPTION)
Calculation:
4,760 ÷ 150 = 31.73 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
31.73
Calculation:
31.73 x 144 = 4,569.12 sq. in. of Code Required Ventilation
Square Inches Provided:
(48 x 98.75) = 4,740 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.
Vent Solutions