Contact Us
(877) 324-0444
Search
Products
Composition Shingle Vents
Clay Tile Vents
Concrete Tile Vents
Natural Slate Vents
Synthetic Shake and Slate Vents
Wood Shake Vents
Universal Direct Deck
Fire&Ice® Vents
Fire&Ice® Profile Specific Vents for Concrete, Clay & Synthetic Tile Roofs
Fire&Ice® Composition Shingle, Synthetic Shake & Slate Vents
Gallery
Services
Pre-Construction Services
Attic Ventilation Analysis Request Form
Benefits of Attic Ventilation
O’Hagin University
AIA Approved Continuing Education
Resources
Approvals
Architectural Resources & Drawings
Building Codes
Find a Distributor
Installation Instructions
Limited Warranty
Technical Bulletins
Vent Calculator
Search
Back to Vent Calculator
Print
Address:
26531 Anchorage Ln.
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2957.1'
Required Method:
1/300
Calculation:
2957.1 ÷ 300 = 9.86 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
9.86
Calculation:
9.86 x 144 = 1419.84 sq. in of Code Required Ventilation
Square Inches Provided:
(16 x 97.5) = 1560 sq. in
Square Inches Needed:
9.86 x 144 = 1419.84 sq. in
Vent Placement
High / Exhaust Vents Needed:
8
Low / Intake Vents Needed:
8
Total Vents Needed:
16
concrete Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Wire Mesh
97.5 sq. in
Figures based on independent evaluation reports.