Total Vents:
60
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
30
Low / Intake Vents:
(Within Lower 1/3 of Attic)
30
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
6,000
Code Required Method:
1/150 (EXCEPTION)
Calculation:
6,000 ÷ 150 = 40 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
40
Calculation:
40 x 144 = 5,760 sq. in. of Code Required Ventilation
Square Inches Provided:
(60 x 98.75) = 5,925 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.