Address:
4637 Park Drive, Carlsbad, CA 92008
Total Vents:
118
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
59
Low / Intake Vents:
(Within Lower 1/3 of Attic)
59
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
10,500
Code Required Method:
1/150 (EXCEPTION)
Calculation:
10,500 ÷ 150 = 70 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
70
Calculation:
70 x 144 = 10,080 sq. in. of Code Required Ventilation
Square Inches Provided:
(118 x 86.25) = 10,177.50 sq. in.
concrete Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.
Vent Solutions