Total Vents:
28
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
14
Low / Intake Vents:
(Within Lower 1/3 of Attic)
14
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
5,416
Code Required Method:
1/300 (EXCEPTION)
Calculation:
5,416 ÷ 300 = 18.05 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
18.05
Calculation:
18.05 x 144 = 2,599.20 sq. in. of Code Required Ventilation
Square Inches Provided:
(28 x 97.50) = 2,730 sq. in.
concrete Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?