Total Vents:
16
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
8
Low / Intake Vents:
(Within Lower 1/3 of Attic)
8
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,567
Code Required Method:
1/150 (EXCEPTION)
Calculation:
1,567 ÷ 150 = 10.45 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
10.45
Calculation:
10.45 x 144 = 1,504.80 sq. in. of Code Required Ventilation
Square Inches Provided:
(16 x 98.75) = 1,580 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?