Total Vents:
48
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
24
Low / Intake Vents:
(Within Lower 1/3 of Attic)
24
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
4,831
Code Required Method:
1/150 (EXCEPTION)
Calculation:
4,831 ÷ 150 = 32.21 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
32.21
Calculation:
32.21 x 144 = 4,638.24 sq. in. of Code Required Ventilation
Square Inches Provided:
(48 x 86.25) = 4,140 sq. in.
concrete Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.