Address:
607 VIA DE LA PAZ - LOS ANGELES, CA 90272
Total Vents:
2
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
1
Low / Intake Vents:
(Within Lower 1/3 of Attic)
1
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
236.28
Code Required Method:
1/300 (EXCEPTION)
Calculation:
236.28 ÷ 300 = 0.79 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
0.79
Calculation:
0.79 x 144 = 113.76 sq. in. of Code Required Ventilation
Square Inches Provided:
(2 x 64.80) = 129.60 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 64.80 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?