Address:
11640 Treadwell Drive 92064
Total Vents:
26
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
13
Low / Intake Vents:
(Within Lower 1/3 of Attic)
13
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
4,780
Code Required Method:
1/300 (EXCEPTION)
Calculation:
4,780 ÷ 300 = 15.93 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
15.93
Calculation:
15.93 x 144 = 2,293.92 sq. in. of Code Required Ventilation
Square Inches Provided:
(26 x 88.87) = 2,310.62 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 88.87 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?