Address:
6070: Mike Wohlers 8520 Bent Creek Way Naples, FL 34114
Total Vents:
16
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
8
Low / Intake Vents:
(Within Lower 1/3 of Attic)
8
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2,758
Code Required Method:
1/300 (EXCEPTION)
Calculation:
2,758 ÷ 300 = 9.19 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
9.19
Calculation:
9.19 x 144 = 1,323.36 sq. in. of Code Required Ventilation
Square Inches Provided:
(16 x 86.25) = 1,380 sq. in.
concrete Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?