Total Vents:
52
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
26
Low / Intake Vents:
(Within Lower 1/3 of Attic)
26
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
4,500
Code Required Method:
1/150 (STANDARD)
Calculation:
4,500 ÷ 150 = 30 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
30
Calculation:
30 x 144 = 4,320 sq. in. of Code Required Ventilation
Square Inches Provided:
(52 x 86.25) = 4,485 sq. in.
concrete Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.
Vent Solutions