Address:
3362 Greendale Ave Rosemead Ca. 91770
Total Vents:
14
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
7
Low / Intake Vents:
(Within Lower 1/3 of Attic)
7
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
989
Code Required Method:
1/150 (STANDARD)
Calculation:
989 ÷ 150 = 6.59 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
6.59
Calculation:
6.59 x 144 = 948.96 sq. in. of Code Required Ventilation
Square Inches Provided:
(14 x 72) = 1,008 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.