Total Vents:
32
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
16
Low / Intake Vents:
(Within Lower 1/3 of Attic)
16
Metal Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
5,157
Code Required Method:
1/300 (EXCEPTION)
Calculation:
5,157 ÷ 300 = 17.19 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
17.19
Calculation:
17.19 x 144 = 2,475.36 sq. in. of Code Required Ventilation
Square Inches Provided:
(32 x 78) = 2,496 sq. in.
Standing Seam metal
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 78 sq. in.
Figures based on independent evaluation reports.