Address:
5677 Wild View Way
Total Vents:
16
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
8
Low / Intake Vents:
(Within Lower 1/3 of Attic)
8
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,570
Code Required Method:
1/150 (EXCEPTION)
Calculation:
1,570 ÷ 150 = 10.47 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
10.47
Calculation:
10.47 x 144 = 1,507.68 sq. in. of Code Required Ventilation
Square Inches Provided:
(16 x 86.25) = 1,380 sq. in.
clay Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?