Total Vents:
44
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
22
Low / Intake Vents:
(Within Lower 1/3 of Attic)
22
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
4,521
Code Required Method:
1/150 (STANDARD)
Calculation:
4,521 ÷ 150 = 30.14 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
30.14
Calculation:
30.14 x 144 = 4,340.16 sq. in. of Code Required Ventilation
Square Inches Provided:
(44 x 98.75) = 4,345 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.