Total Vents:
40
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
20
Low / Intake Vents:
(Within Lower 1/3 of Attic)
20
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
3,931
Code Required Method:
1/150 (STANDARD)
Calculation:
3,931 ÷ 150 = 26.21 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
26.21
Calculation:
26.21 x 144 = 3,774.24 sq. in. of Code Required Ventilation
Square Inches Provided:
(40 x 98.75) = 3,950 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.