Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
8239'
Required Method:
1/300
Calculation:
8239 ÷ 300 = 27.46 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation
27.46
Calculation:
27.46 x 144 = 3954.24 sq. in of Code Required Ventilation
Select Material and Determine Vents Required
Material:
concrete Tile
Placement
Square Inches Provided:
(46 x 97.5) = 4485 sq. in
Square Inches Needed:
27.46 x 144 = 3954.24 sq. in
High / Exhaust Vents Needed:
23
Low / Intake Vents Needed:
23
Total Vents Needed:
46
Material:
concrete Tile
Product:
High Profile - "S"
Tile Roof Drawing