Address:
210 classic court rohnert park ca 94928
Total Vents:
46
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
23
Low / Intake Vents:
(Within Lower 1/3 of Attic)
23
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
3,432
Code Required Method:
1/150 (EXCEPTION)
Calculation:
3,432 ÷ 150 = 22.88 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
22.88
Calculation:
22.88 x 144 = 3,294.72 sq. in. of Code Required Ventilation
Square Inches Provided:
(46 x 72) = 3,312 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.