Total Vents:
6
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
3
Low / Intake Vents:
(Within Lower 1/3 of Attic)
3
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
876
Code Required Method:
1/300 (EXCEPTION)
Calculation:
876 ÷ 300 = 2.92 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
2.92
Calculation:
2.92 x 144 = 420.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(6 x 77.63) = 465.78 sq. in.
concrete Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 77.63 sq. in.
Figures based on independent evaluation reports.