Total Vents:
18
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
9
Low / Intake Vents:
(Within Lower 1/3 of Attic)
9
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2,381
Code Required Method:
1/300 (EXCEPTION)
Calculation:
2,381 ÷ 300 = 7.94 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
7.94
Calculation:
7.94 x 144 = 1,143.36 sq. in. of Code Required Ventilation
Square Inches Provided:
(18 x 64.80) = 1,166.40 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 64.80 sq. in.
Figures based on independent evaluation reports.