87WH+G8C Holcomb Village, California
Total Vents:
26
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
13
Low / Intake Vents:
(Within Lower 1/3 of Attic)
13
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,750
Code Required Method:
1/150 (EXCEPTION)
Calculation:
1,750 ÷ 150 = 11.67 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
11.67
Calculation:
11.67 x 144 = 1,680.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(26 x 64.80) = 1,684.80 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 64.80 sq. in.
Figures based on independent evaluation reports.