Total Vents:
50
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
25
Low / Intake Vents:
(Within Lower 1/3 of Attic)
25
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
9,845
Code Required Method:
1/300 (EXCEPTION)
Calculation:
9,845 ÷ 300 = 32.82 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
32.82
Calculation:
32.82 x 144 = 4,726.08 sq. in. of Code Required Ventilation
Square Inches Provided:
(50 x 97.50) = 4,875 sq. in.
concrete Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.