Address:
317 Margaret Ave Los Angeles CA 90022
Total Vents:
274
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
137
Low / Intake Vents:
(Within Lower 1/3 of Attic)
137
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2,800
Code Required Method:
1/150 (EXCEPTION)
Calculation:
2,800 ÷ 150 = 18.67 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
18.67
Calculation:
18.67 x 144 = 2,688.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(274 x 98.75) = 27,057.50 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.
Vent Solutions