Total Vents:
168
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
84
Low / Intake Vents:
(Within Lower 1/3 of Attic)
84
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
15,000
Code Required Method:
1/150 (EXCEPTION)
Calculation:
15,000 ÷ 150 = 100 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
100
Calculation:
100 x 144 = 14,400 sq. in. of Code Required Ventilation
Square Inches Provided:
(168 x 97.50) = 16,380 sq. in.
concrete Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.