Total Vents:
2
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
1
Low / Intake Vents:
(Within Lower 1/3 of Attic)
1
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
50
Code Required Method:
1/150 (EXCEPTION)
Calculation:
50 ÷ 150 = 0.33 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
0.33
Calculation:
0.33 x 144 = 47.52 sq. in. of Code Required Ventilation
Square Inches Provided:
(2 x 97.50) = 195 sq. in.
concrete Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.