Address:
12656 Crescent Meadow Court Moorpark
Total Vents:
8
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
4
Low / Intake Vents:
(Within Lower 1/3 of Attic)
4
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,200
Code Required Method:
1/150 (EXCEPTION)
Calculation:
1,200 ÷ 150 = 8 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
8
Calculation:
8 x 144 = 1,152 sq. in. of Code Required Ventilation
Square Inches Provided:
(8 x 72) = 576 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.
Vent Solutions