Address:
33512 Valle Rd, San Juan Capistrano, CA 92675
Total Vents:
4
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
2
Low / Intake Vents:
(Within Lower 1/3 of Attic)
2
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
746
Code Required Method:
1/300 (EXCEPTION)
Calculation:
746 ÷ 300 = 2.49 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
2.49
Calculation:
2.49 x 144 = 358.56 sq. in. of Code Required Ventilation
Square Inches Provided:
(4 x 98.75) = 395 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?