Total Vents:
64
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
32
Low / Intake Vents:
(Within Lower 1/3 of Attic)
32
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
4,700
Code Required Method:
1/150 (EXCEPTION)
Calculation:
4,700 ÷ 150 = 31.33 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
31.33
Calculation:
31.33 x 144 = 4,511.52 sq. in. of Code Required Ventilation
Square Inches Provided:
(64 x 72) = 4,608 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.