3540 FARRON ST
Total Vents:
72
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
36
Low / Intake Vents:
(Within Lower 1/3 of Attic)
36
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
5,324
Code Required Method:
1/150 (EXCEPTION)
Calculation:
5,324 ÷ 150 = 35.49 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
35.49
Calculation:
35.49 x 144 = 5,110.56 sq. in. of Code Required Ventilation
Square Inches Provided:
(72 x 72) = 5,184 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.