Address:
988 CALLE PLANTADOR, THOUSAND OAKS, CA. 91360
Total Vents:
8
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
4
Low / Intake Vents:
(Within Lower 1/3 of Attic)
4
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
565
Code Required Method:
1/150 (EXCEPTION)
Calculation:
565 ÷ 150 = 3.77 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
3.77
Calculation:
3.77 x 144 = 542.88 sq. in. of Code Required Ventilation
Square Inches Provided:
(8 x 88.87) = 710.96 sq. in.
clay Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
1/8" Noncombustible, Corrosion-Resistant Wire Mesh 88.87 sq. in.
Figures based on independent evaluation reports.