Address:
2296 CUTLER AVENUE
Total Vents:
6
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
3
Low / Intake Vents:
(Within Lower 1/3 of Attic)
3
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
475
Code Required Method:
1/150 (EXCEPTION)
Calculation:
475 ÷ 150 = 3.17 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
3.17
Calculation:
3.17 x 144 = 456.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(6 x 98.75) = 592.50 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?