Address:
4923 N AGUIRRE RD TUCSON, AZ. 85653
Total Vents:
28
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
14
Low / Intake Vents:
(Within Lower 1/3 of Attic)
14
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2,450
Code Required Method:
1/150 (EXCEPTION)
Calculation:
2,450 ÷ 150 = 16.33 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
16.33
Calculation:
16.33 x 144 = 2,351.52 sq. in. of Code Required Ventilation
Square Inches Provided:
(28 x 97.50) = 2,730 sq. in.
concrete Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?