Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
5093'
Required Method:
1/150
Calculation:
5093 ÷ 150 = 33.95 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation
33.95
Calculation:
33.95 x 144 = 4888.80 sq. in of Code Required Ventilation
Select Material and Determine Vents Required
Material:
concrete Tile
Placement
Square Inches Provided:
(68 x 72) = 4896 sq. in
Square Inches Needed:
33.95 x 144 = 4888.80 sq. in
High / Exhaust Vents Needed:
34
Low / Intake Vents Needed:
34
Total Vents Needed:
68
Material:
concrete Tile
Product:
Low Profile - "Flat"
Tile Roof Drawing
Benefits of Attic Ventilation
1. Extends the roof's life
2. Curb appeal
3. Balanced System
4. Fits with Solar Systems
5. Validate the Warranty
6. Enhances Above-Sheathing Ventilation (ASV)
7. Reduces Moisture/Removes Trapped Gases
8. Energy conservation