Total Vents:
38
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
19
Low / Intake Vents:
(Within Lower 1/3 of Attic)
19
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
6,629
Code Required Method:
1/300 (EXCEPTION)
Calculation:
6,629 ÷ 300 = 22.10 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
22.10
Calculation:
22.10 x 144 = 3,182.40 sq. in. of Code Required Ventilation
Square Inches Provided:
(38 x 97.50) = 3,705 sq. in.
concrete Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.