Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
5652'
Required Method:
1/150
Calculation:
5652 ÷ 150 = 37.68 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation
37.68
Calculation:
37.68 x 144 = 5425.92 sq. in of Code Required Ventilation
Select Material and Determine Vents Required
Material:
concrete Tile
Placement
Square Inches Provided:
(76 x 72) = 5472 sq. in
Square Inches Needed:
37.68 x 144 = 5425.92 sq. in
High / Exhaust Vents Needed:
38
Low / Intake Vents Needed:
38
Total Vents Needed:
76
Material:
concrete Tile
Product:
Low Profile - "Flat"
Tile Roof Drawing