Total Vents:
76
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
38
Low / Intake Vents:
(Within Lower 1/3 of Attic)
38
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
5,652
Code Required Method:
1/150 (EXCEPTION)
Calculation:
5,652 ÷ 150 = 37.68 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
37.68
Calculation:
37.68 x 144 = 5,425.92 sq. in. of Code Required Ventilation
Square Inches Provided:
(76 x 72) = 5,472 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.