Address:
5663 Irvington place Los Angeles ca 90042
Total Vents:
18
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
9
Low / Intake Vents:
(Within Lower 1/3 of Attic)
9
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,680
Code Required Method:
1/150 (EXCEPTION)
Calculation:
1,680 ÷ 150 = 11.20 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
11.20
Calculation:
11.20 x 144 = 1,612.80 sq. in. of Code Required Ventilation
Square Inches Provided:
(18 x 98.75) = 1,777.50 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?